VIS CAM 300/400 Installation Manual
Appendix E: Moxa N-Port 5232 Configuration
Serial port 1 settings:
Port alias: D1 – enter desired name of this specific serial port.
Baud rate: 9600
– specify the desired baud rate of the serial port – the TLS200 light
sensor requires 9600 as standard.
Data bits: 8
– specify the desired size of the data bits used - the TLS200 light sensor
requires 8 as standard.
Stop bits: 2
– Specify the desired size of the stop bits used - the TLS200 light sensor
requires 2 as standard.
Parity: None – feature not used in communication with the light sensor.
Flow control: None - feature not used in communication with the light sensor.
Fifo: Enable
- the TLS200 light sensor requires FIFO as standard.
Interface: RS-485 2wire
– the communication with the TLS-300 light sensor is standard
2-wire RS-485.
Enable – apply the above settings to all serial ports – rename port 2 port alias to D0.
FIGURE 89. Standard configuration of Serial settings for port 1: